Fuel storage rules for tree yards: OSHA container limits and EPA oil thresholds
OSHA's flammable liquids standard sets container, cabinet and tank limits from 1 pint to 660 gallons. EPA's oil spill rule reaches facilities holding more than 1,320 gallons above ground.
Checked against the sources at the bottom of this page on October 21, 2026. Rules, fees and pay change: the source has the last word.
This page reports what the official source says. It is not legal advice: ask the office named here. Two federal sources cover fuel stored at a yard: the Occupational Safety and Health Administration standard on flammable liquids, 29 CFR 1910.106, and the Environmental Protection Agency oil spill rule, 40 CFR part 112.
What OSHA counts as a flammable liquid
Paragraph (a)(19) of 1910.106 defines a flammable liquid as any liquid with a flashpoint at or below 199.4 °F (93 °C). It sorts them into four categories by flashpoint and boiling point, not by product name.
- Category 1: flashpoint below 73.4 °F (23 °C) and boiling point at or below 95 °F (35 °C).
- Category 2: flashpoint below 73.4 °F (23 °C) and boiling point above 95 °F (35 °C).
- Category 3: flashpoint from 73.4 °F (23 °C) up to 140 °F (60 °C).
- Category 4: the liquids with a higher flashpoint, up to the 199.4 °F ceiling.
Containers, cabinets and rooms under paragraph (d)
Paragraph (d)(1) covers drums and other containers up to 60 gallons each and portable tanks up to 660 gallons each. It leaves out bulk plants, service stations, refineries, chemical plants and distilleries. It also leaves out the fuel tank of a motor vehicle, aircraft, boat, or portable or stationary engine, and paint or maintenance mixtures kept no longer than 30 days.
Table H-12 sets the largest container for each category.
| Container type | Category 1, 2, 3, 4 |
|---|---|
| Glass or approved plastic | 1 pint, 1 quart, 1 gallon, 1 gallon |
| Metal (other than DOT drums) | 1 gallon, 5 gallons, 5 gallons, 5 gallons |
| Safety cans | 2 gallons, 5 gallons, 5 gallons, 5 gallons |
| Metal drums (DOT specifications) | 60 gallons in every category |
| Approved portable tanks | 660 gallons in every category |
A storage cabinet holds not more than 60 gallons of Category 1, 2 or 3 liquids, or 120 gallons of Category 4. The cabinet limits its inside temperature to 325 °F in a 10-minute fire test. It carries the label "Flammable - Keep Fire Away." An inside storage room needs raised sills or ramps at least 4 inches high at its openings, or a floor at least 4 inches below the floor around it.
Paragraph (d)(5)(i) adds that flammable liquids are not stored so as to limit use of exits, stairways or areas normally used to leave a building. Paragraph (e)(2) covers industrial plants that use flammable liquids only incidentally. Outside a cabinet or storage room, one fire area of a building holds at most 25 gallons of Category 1 in containers. For Category 2, 3 or 4 the caps are 120 gallons in containers, or 660 gallons in a single portable tank.
The EPA oil storage threshold
Under 40 CFR 112.1(b), the oil spill rule applies to a non-transportation-related facility that stores, uses or transfers oil and could reasonably be expected to discharge it to navigable waters or shorelines. Paragraph (d)(2) exempts a facility that has both 42,000 U.S. gallons or less of completely buried storage and 1,320 U.S. gallons or less of aggregate aboveground storage. Only containers of 55 U.S. gallons or more count toward the 1,320.
The EPA page on the spill plan, written for marinas, prints the threshold two ways. One passage says marinas that store more than 1,320 gallons usually need a plan. Another says a total of 1,320 gallons or more means a plan is needed. The regulation's wording is "1,320 U.S. gallons or less" for the exemption.
The same EPA page describes the plan as a written document covering the facility, the petroleum storage containment, inspections and a site diagram showing tanks, drainage and other details. A Professional Engineer certifies it, unless the facility qualifies to self-certify. That route is open to a facility with 10,000 gallons or less in aggregate aboveground oil storage. The facility must also have had no single oil discharge to navigable waters over 1,000 U.S. gallons, and no two discharges each over 42 U.S. gallons within twelve months, in the three years before certification. The plan is kept at the facility for inspection and is not filed with EPA unless EPA asks.
NFPA 30 and the test method OSHA cites
The National Fire Protection Association lists NFPA 30 as the Flammable and Combustible Liquids Code. OSHA's own paragraphs cite a fire test method, NFPA 251-1969, for cabinet and room construction.
Sources
- U.S. Occupational Safety and Health Administration, 29 CFR 1910.106 Flammable liquids, read October 21, 2026
- U.S. Environmental Protection Agency, Spill Prevention, Control and Countermeasure guide for marinas and boat owners (page updated June 26, 2026), read October 21, 2026
- U.S. Code of Federal Regulations, 40 CFR 112.1 General applicability, via Cornell Legal Information Institute, read October 21, 2026
- National Fire Protection Association, NFPA 30 Flammable and Combustible Liquids Code, product page (title only), read October 21, 2026