HSE GS6: avoiding danger from overhead power lines, and where it meets tree work
HSE's GS6 sets a 10 m planning distance for work near overhead lines and gives exclusion zones from 1 m to 7 m. It names arboriculture only in a pointer, and HSE's tree work page carries the tree-specific wording.
Checked against the sources at the bottom of this page on October 16, 2026. Rules, fees and pay change: the source has the last word.
This page reports what the official source says. It is not legal advice: ask the office named here. The sources are HSE's guidance note GS6, Avoiding danger from overhead power lines, fourth edition, published in 2013, and HSE's tree work page on working near power lines and cables. HSE's electrical safety topic page lists overhead power lines among its publications and case studies.
What GS6 is
HSE calls GS6 a general series guidance note for people planning work near overhead lines where wires could be touched. It is aimed mainly at employers and employees who supervise or control work near live overhead lines. HSE's web page for GS6 is dated 2013, with a page update in November 2021.
GS6 does not discuss tree work in its main text. Paragraph 32 names construction, agriculture, horticulture, forestry and arboriculture as sectors with industry-specific guidance based on it. Its further reading for arboriculture and forestry points to HSE's treework power lines page and an Energy Networks Association leaflet on tree trimming.
The 10 m distance and the order of controls
GS6 says risks should be managed when work is planned within 10 m, measured at ground level horizontally from below the nearest wire. It tells readers to assume a line is live until its owner confirms it is dead. High-voltage lines are to be treated as uninsulated, and so are low-voltage lines whose insulation may be in poor condition.
The order of controls runs from removing the risk to controlling it. GS6 lists avoiding work where wires could be touched, diverting a line or replacing it with underground cable, and switching the line off temporarily. When the line can be neither diverted nor switched off and the work cannot be done safely, GS6 states that it should not be done at all.
The risk assessment factors include the voltage and height of the wires, the reach of machinery, the safe clearance distance, the site conditions and the competence and supervision of those on site. GS6 adds that a suitably trained person should measure wire height with non-contact devices.
Safety zones and exclusion zones
Where nothing works under the line, GS6 describes ground-level barriers that set up a safety zone. The zone extends 6 m horizontally from the nearest wire on either side. The owner of the line may advise a wider zone.
For short-duration ground work where contact could occur, GS6 refers to the Energy Networks Association publication Look Out Look Up. It gives minimum exclusion zones by voltage, and GS6 states that no part of plant, ladders, poles or hand tools may encroach within them.
| Line voltage | Exclusion zone | Minimum height above ground (Figure 4) |
|---|---|---|
| Low voltage | 1 m | 5.2 m, or 5.8 m above roads |
| 11 kV | 3 m | 5.2 m, or 5.8 m above roads |
| 33 kV | 3 m | 5.2 m, or 5.8 m above roads |
| 132 kV | 6 m | 6.7 m |
| 275 kV | 7 m | 7 m |
| 400 kV | 7 m | 7.3 m |
GS6 notes that the legal minimum height varies with voltage and that Energy Networks Association Technical Specification 43-8 publishes recommended clearances to structures. Its emergency points are that nobody touches the wires, that wires are assumed live even when they are not arcing, and that anyone near a damaged wire stays away until the owner advises that it is safe.
The law GS6 cites
Annex 1 of GS6 lists the Health and Safety at Work etc. Act 1974 and the Management of Health and Safety at Work Regulations 1999. It lists regulation 9 of the Provision and Use of Work Equipment Regulations 1998 on training, and the Electricity Safety, Quality and Continuity Regulations 2002 on the height of lines. Regulation 14 of the Electricity at Work Regulations 1989 covers live work, including work so near live overhead lines that there is a risk of injury.
HSE's tree work page
HSE's tree work page, updated September 22, 2026, applies a risk-based approach to arboricultural, aerial and ground work within 10 m of overhead power lines. It measures that distance at ground level horizontally from below the nearest wire. It also covers work beyond 10 m that could breach the distance, such as falling trees, timber and debris, or MEWPs and cranes that could collapse within 10 m.
HSE's first choice is to work dead, with the power turned off. Any decision to work live must be justified, documented and meet regulation 14 of the Electricity at Work Regulations. It limits tree work near live equipment to work as recommended by the network operator, using the operator's procedures and appropriately qualified people. Where published guidance on safety distances and working techniques conflicts, HSE points to the network operator's advice before work goes ahead.
Sources
- Health and Safety Executive, GS6 Avoiding danger from overhead power lines, fourth edition, web page, read October 16, 2026
- Health and Safety Executive, GS6 Avoiding danger from overhead power lines, fourth edition, PDF, published 2013, read October 16, 2026
- Health and Safety Executive, Working near power lines and cables, tree work, updated September 22, 2026, read October 16, 2026
- Health and Safety Executive, Electrical safety topic page, updated October 14, 2025, read October 16, 2026