Insulated pole saws near power lines: what ASTM F711 and IEC 60855 insulate, and what regulators say
ASTM F711 and IEC 60855-1 cover fibreglass rods and tubes for live line tools, not saws as a whole. OSHA 1910.269(r)(1)(iv) allows branches near energised conductors to be removed only with insulating equipment.
Checked against the sources at the bottom of this page on October 19, 2026. Rules, fees and pay change: the source has the last word.
This page reports what the official source says. It is not legal advice: ask the office named here. It gives no clearance distances. The wording comes from the ASTM F711 store page, the AFNOR catalogue entries for IEC 60855-1, the OSHA line-clearance tree trimming eTool and 29 CFR 1910.269.
The standards at a glance
| Standard | Covers | Does not cover |
|---|---|---|
| ASTM F711-26, Fiberglass-Reinforced Plastic (FRP) Rod and Tube Used in Live Line Tools | Insulating rods and foam-filled tubes made from fiberglass-reinforced plastic, intended for live line tools | Rods and tubes from other materials. Fittings and attachments for complete tools |
| IEC 60855-1:2016, Live working, insulating foam-filled tubes and solid rods, Part 1 | Foam-filled tubes and solid rods of circular cross-section, made of synthetic materials with reinforced fibreglass, for tools, devices and equipment for live working above 1 kV | Rods and tubes of other than circular cross-section, which the 2009 entry says a possible Part 2 would cover |
ASTM F711
ASTM F711-26 is listed as an active standard, last updated March 9, 2026, under Committee F18. Its scope covers the technical characteristics of and test methods for insulating rods and foam-filled tubes made from fiberglass-reinforced plastic that are intended for live line tools.
It names four types of test: design, sample, routine and acceptance. The properties tested include wicking, bending deflection, horizontal crush, tension, shear, compression, modulus of elasticity and mechanical aging, with dielectric current and leakage.
Fittings and attachments to the rods and tubes for complete tools are outside the scope, and so are rods and tubes of other materials.
IEC 60855
AFNOR's catalogue lists IEC 60855:1985, Insulating foam-filled tubes and solid rods for live working, as cancelled. The first edition of IEC 60855-1 was published in October 2009 and is also cancelled. IEC 60855-1:2016, published April 2016, is the current second edition.
The 2016 edition applies to insulating foam-filled tubes and solid rods of circular cross-section, made of synthetic materials with reinforced fibreglass. They are intended for tools, devices and equipment for live working on electrical systems above 1 kV. The edition cancels and replaces the 2009 first edition and constitutes a technical revision.
The 2009 entry notes that technical committee 78 was considering IEC 60855-2 for tubes and rods of other cross-section. Its ICS codes are 29.260.01, 13.260 and 29.240.20.
OSHA 1910.269 on tools and line-clearance tree trimming
Paragraph (j)(1) of 29 CFR 1910.269 sets minimum tests for live-line tool rods, tubes and poles. A tool made of FRP shall withstand 328,100 volts per meter (100,000 volts per foot) of length for 5 minutes. A wooden tool shall withstand 246,100 volts per meter (75,000 volts per foot) for 3 minutes. A tool may instead withstand other tests the employer can demonstrate are equivalent.
A note to (j)(1)(i) says live-line tools using rod and tube that meet ASTM F711-02 (2007) are deemed to comply with paragraph (j)(1).
Paragraph (j)(2) covers condition. Each live-line tool is wiped clean and visually inspected for defects before use each day. Tools used for primary employee protection are removed from service every 2 years, and whenever a defect or contamination is present after wiping, for examination, cleaning, repair and testing.
Paragraph (r) covers line-clearance tree trimming. Under (r)(1)(iv), branches contacting exposed energized conductors or equipment, or within the distances in Tables R-5 to R-8, may be removed only through the use of insulating equipment.
A note to (r)(1)(iv) says a tool constructed of a material that the employer can demonstrate has insulating qualities meeting paragraph (j)(1) is considered as insulated if the tool is clean and dry. Paragraph (r)(1) does not apply to qualified employees.
The OSHA eTool
OSHA's eTool on line-clearance tree trimming describes three qualification levels: unqualified employees, 269-qualified employees and line-clearance tree trimmers. Line-clearance tree trimmers use only insulated tools and equipment to remove branches and limbs in contact with, or within the minimum approach distance of, energized parts. The eTool cites 1910.269(r)(1)(iv).
The eTool notes that 1910.269 does not apply to tree trimming operations performed by unqualified employees, whose work practices fall under Subpart S, particularly 1910.333(c)(3).
Gaps in the sources
The word pole saw does not appear in any of the four sources, and none gives a voltage rating for one. The power lines guide on this site is the guide to power lines and tree work.
Sources
- ASTM International, F711-26 Standard Specification for Fiberglass-Reinforced Plastic (FRP) Rod and Tube Used in Live Line Tools, store page, read October 19, 2026
- AFNOR Editions, IEC 60855-1:2009 catalogue entry, with the replacing IEC 60855-1:2016, read October 19, 2026
- OSHA, Overhead Line Work eTool, Line-Clearance Tree Trimming Operations, read October 19, 2026
- OSHA, 29 CFR 1910.269 Electric power generation, transmission, and distribution, paragraphs (j) and (r), eCFR, read October 19, 2026