Ontario's O. Reg. 213/91 section 188(2) sets 3 metres up to 150,000 volts, 4.5 metres to 250,000 volts and 6 metres above. The Electrical Utility Safety Rules take utility work out of section 188, and 444B Utility Arborists work within the limits.

Checked against the sources at the bottom of this page on October 15, 2026. Rules, fees and pay change: the source has the last word.

This page reports what the official source says. It is not legal advice: ask the office named here. British Columbia is on the main approach distances page.

Ontario section 188

O. Reg. 213/91, the construction projects regulation, requires minimum safe distances when objects could be near live overhead powerlines. The Infrastructure Health and Safety Association (IHSA) and Ontario.ca print the section 188(2) table.

Normal phase-to-phase voltage ratingMinimum distance
750 or more volts, but no more than 150,000 volts3 metres
More than 150,000 volts, but no more than 250,000 volts4.5 metres
More than 250,000 volts6 metres

The written measures under section 188 include warning devices and a sign, written notice of the hazard to the operator, and a competent worker designated as a signaller. The signaller warns the operator when any part of the equipment, load or hoist line may approach the minimum distance. Section 189 allows an exemption only under two conditions. Protective devices and equipment are installed under the authority of the conductor's owner, with written procedures that protect workers from shock and burn. The workers use that equipment and follow those procedures.

The utility safety rules exemption

Section 181 of O. Reg. 213/91 says electrical work performed on or near electrical transmission or distribution systems shall be performed in accordance with the Electrical Utility Safety Rules published by IHSA and revised 2019. Under subsection 181(2), sections 182, 187, 188, 189, 190, 191 and 193 do not apply to that work when it is performed in accordance with the rules. Ontario.ca restates this: the section 188 distances do not apply in two cases, work done per the Electrical Utility Safety Rules, or conditions met under section 189.

The Electrical Safety Authority (ESA) vegetation management guideline draws the line for trees. It says arborists and landscapers are not qualified to work in the vicinity of energized powerlines and must follow the limits of approach in section 188(2). Utility Arborists who are 444B certified are authorized to prune, clear vegetation, fell or remove trees within those limits.

The ESA guideline prints 3 metres for primary distribution lines of 750 to 150,000 volts. For transmission lines it prints 4.5 metres and 6 metres.

Alberta

The Alberta government bulletin LH004, updated March 31, 2023, covers changes to Parts 17 and 40 of the Occupational Health and Safety Code, effective March 31, 2023. The "safe limit of approach distance" is the safe working distance from overhead power lines. The distances are listed in Schedule 4 of the OHS Code. The bulletin does not print the values.

Employers must notify the electric utility, rural electrification association or industrial power producer that owns a line before work is done or equipment is operated near it. Workers share with the employer the responsibility for keeping the Schedule 4 distances. All overhead power lines must be assumed to be energized. The exemption to section 225 applies to any utility worker working in accordance with CAN/ULC-S801-14.

Saskatchewan

SaskPower's Minimum Approach Distance standard applies to work near or on exposed energized lines above 50 volts by workers on behalf of SaskPower. It sets distances for Qualified Electrical Workers using the IEEE 516 method and the Occupational Health and Safety Regulations, 2020. They are approved by a professional engineer and meet CAN/ULC-S801-14. The table reads in metres, and for voltages not listed the next higher voltage is used.

Nominal phase to phasePhase to ground (m)Phase to phase (m)
750 V0.35-
4.16 kV0.65-
15 kV0.70-
25 kV0.75-
34.5 kV0.80-
72 kV0.951.25
138 kV1.201.75
230 kV1.802.80

The standard treats workers who are not Qualified Electrical Workers as unqualified persons above 750 volts, except those classified as utility tree trimmers under Part 30-16(1) of the Occupational Health and Safety Regulations, 2020. For an unqualified person it points to the Non-electrical Workers, Material, Equipment column of Table 19 in those regulations. That table's values are not printed in the standard.