Minimum approach distances in the UK, Ireland and New Zealand
Britain's HSE draws a 10 m line for managing risk, Ireland's HSA code sets a 6 m or 10 m hazard zone, and WorkSafe New Zealand names 4 m and 0.5 m for low voltage lines.
Checked against the sources at the bottom of this page on October 18, 2026. Rules, fees and pay change: the source has the last word.
This page reports what the official source says. It is not legal advice: ask the office named here. The three countries word their distances differently, so the table sets each figure beside the thing it measures.
| Country and source | Distance | What it measures |
|---|---|---|
| Great Britain, HSE guidance note GS6 (fourth edition, 2013) | 10 m | Horizontal distance at ground level from below the nearest wire, inside which the risks are to be managed |
| Great Britain, HSE guidance note GS6 | 6 m | Width of a ground-level safety zone on either side of the nearest wire where barriers are used |
| Great Britain, Electricity Safety, Quality and Continuity Regulations 2002, regulation 17 | 4.3 m, 5.8 m | Minimum heights of line sections and attached wires above ground |
| Ireland, HSA Code of Practice for Avoiding Danger from Overhead Electricity Lines (second edition, 2019) | 6.0 m | Hazard zone for LV, 10 kV, 20 kV and 38 kV lines |
| Ireland, HSA code | 10.0 m | Hazard zone for 110 kV, 220 kV and 400 kV lines |
| Ireland, ESB Networks tree cutting assessment page | 6 m | Distance from electricity wires or equipment inside which ESB Networks asks to be contacted before trees or hedges are cut |
| New Zealand, WorkSafe New Zealand guide to low voltage overhead lines | 4 m | Minimum approach distance without the property owner's written consent |
| New Zealand, WorkSafe New Zealand guide | 0.5 m | Minimum approach distance with the owner's written consent |
Great Britain
HSE's guidance note GS6, Avoiding danger from overhead power lines, says to manage the risks for any work within 10 m, measured at ground level horizontally from below the nearest wire. HSE's tree work page uses the same 10 m. It adds a second case: work more than 10 m away that could still reach the line, such as a falling tree or a crane or platform that collapses.
GS6 treats every high-voltage line as uninsulated. A line counts as live until its owner has confirmed it is dead. Where ground-level barriers are used, the safety zone runs 6 m either side of the nearest wire, and the line owner may call for more. For ground-level work under a line that cannot be switched off, GS6 cites the Energy Networks Association's exclusion zones. They are 1 m for low voltage, 3 m for 11 kV and 33 kV, 6 m for 132 kV, and 7 m for 275 kV and 400 kV. GS6 says the line's owner can advise on safe clearance distances.
The HSE tree work page puts the first choice as work done dead, with the power off. Live work has to be justified and documented under regulation 14 of the Electricity at Work Regulations. The network operator may switch the power off, refine the safety distances or send a specialised utility arboricultural contractor. Where published guidance conflicts on distances, the operator's advice is to be sought.
Heights of the lines
Regulation 17 of the Electricity Safety, Quality and Continuity Regulations 2002 sets minimum heights by voltage in Schedule 2, one column for road crossings and one for other points. A section that is not over a road and is surrounded by insulation, or connected with earth, falls outside that rule. So does an uninsulated connection that links equipment on a support to a line and is at least 4.3 m above ground. Any wire or cable on a support carrying a line must be at least 5.8 m above a road accessible to vehicles. Schedule 2 gives 5.8 m over roads and 5.2 m elsewhere for nominal voltages not exceeding 33,000 volts. The next bands are 6 m for lines above 33,000 and up to 66,000 volts, 6.7 m up to 132,000 volts, 7 m up to 275,000 volts and 7.3 m up to 400,000 volts. GS6 prints the heights in a figure: 7 m for 275 kV, 7.3 m for 400 kV, 6.7 m for 132 kV, and 5.2 m for the lower voltages (5.8 m above roads).
Ireland
The HSA's Code of Practice for Avoiding Danger from Overhead Electricity Lines, second edition, came into effect on May 1, 2019 and replaced the 2008 code. It defines a hazard zone as a lateral area near a line that must normally be isolated from the work site by physical barriers. Table 1 sets the minimum horizontal distance at 6.0 m for LV, 10 kV, 20 kV and 38 kV lines and 10.0 m for 110 kV, 220 kV and 400 kV lines. For plant, the code adds the falling distance of a fully extended boom to those two distances.
The code also defines an exclusion zone, a region around a live line that must never be breached to avoid arcing or flashover. Its crossing-point table gives a maximum crossing width of 9 metres and a maximum height of 4.2 metres, measured from the original site ground level.
ESB Networks words a separate rule for trees. On its tree cutting assessment page, ESB Networks says trees or hedges within 6 meters of electricity equipment are not to be cut without first contacting it, and offers a free assessment for vegetation inside that distance. For felling, ESB Networks gives double the tree's height on either side of poles or overhead wires. It also says to set a hazard zone of at least 6 meters around poles and support wires.
New Zealand
WorkSafe New Zealand's guide to working near low voltage overhead lines puts the minimum approach distance at 4 m without the property owner's written consent and 0.5 m with it. Below 0.5 m the electricity supply must be isolated, and the owner cannot consent to work that close. The distances are set by law in the New Zealand Electrical Code of Practice for Electrical Safe Distances, NZECP 34.
The guide gives separate distances for people, temporary structures such as scaffolding, and mobile plant such as cranes and platforms. The owner or operator of mobile plant must fix a notice reading WARNING, KEEP CLEAR OF POWER LINES near the operator's position. The guide leaves out vegetation work, high voltage lines and distribution lines. Its scope list names tree trimming, pruning and removal as out of scope. A note in the guide says to seek permission from the electricity distributor before work near high voltage lines or lines the distributor owns. The page was last updated April 19, 2021.
Exclusions in the New Zealand sources
- NZECP 34:2001 states that it does not apply to hazards from trees.
- WorkSafe New Zealand's tables for people and for mobile plant are images, so the plant distances are not printed on this page.
Other countries are in the approach distances by jurisdiction guide, including Australia and Canada.
Sources
- HSE, Avoiding danger from overhead power lines, guidance note GS6 (fourth edition, 2013), read October 16, 2026
- HSE, Working near power lines and cables, tree work pages, read October 16, 2026
- legislation.gov.uk, Electricity Safety, Quality and Continuity Regulations 2002, regulation 17, read October 16, 2026
- Health and Safety Authority, Code of Practice for Avoiding Danger from Overhead Electricity Lines, second edition, May 2019, read October 16, 2026
- ESB Networks, Tree cutting assessment, read October 16, 2026
- legislation.gov.uk, Electricity Safety, Quality and Continuity Regulations 2002, Schedule 2, read October 18, 2026
- Ministry of Consumer Affairs, New Zealand Electrical Code of Practice for Electrical Safe Distances NZECP 34:2001, as linked from WorkSafe New Zealand, read October 18, 2026
- WorkSafe New Zealand, Working near low voltage overhead electric lines, read October 16, 2026