The US SPCC exemption stops at 1,320 US gallons of aggregate aboveground oil storage, counting containers of 55 gallons or more. GOV.UK guidance recommends bund sizes and a spill kit, and Canada ties reporting to harm.
Checked against the sources at the bottom of this page on October 16, 2026. Rules, fees and pay change: the source has the last word.
This page reports what the official source says. It is not legal advice: ask the office named here.
United States: where 40 CFR 112.1 applies
Part 112 sets out Spill Prevention, Control, and Countermeasure (SPCC) requirements. Section 112.1(b) applies to the owner or operator of a non-transportation-related facility that stores, transfers, uses or consumes oil and oil products. The facility must be one that, because of its location, could reasonably be expected to discharge harmful quantities of oil into or upon navigable waters of the United States or adjoining shorelines. It must also hold oil in an aboveground container, a completely buried tank, or a container in standby, seasonal or temporary storage that is not permanently closed.
Section 112.1(d)(2) exempts a facility that meets both of two capacity limits.
| Limit | Figure in 112.1(d)(2) |
|---|---|
| Completely buried storage capacity | 42,000 US gallons or less of oil |
| Aggregate aboveground storage capacity | 1,320 US gallons or less of oil |
For the aboveground figure, only containers of 55 US gallons or more count. The section lists what stays out of the total: permanently closed containers, motive power containers as defined in section 112.2, hot-mix asphalt and its containers, and heating oil containers used solely at a single-family residence. Pesticide application equipment and its mix containers are also left out, as are milk containers.
Section 112.1(e) covers the preparing and carrying out of SPCC Plans. Compliance does not relieve an owner or operator of other federal, state or local laws. Under 112.1(f), the EPA Regional Administrator may still require a plan from a facility under EPA jurisdiction, after a written notice, even where paragraph (d) would exempt it.
United Kingdom: GOV.UK pollution prevention guidance
The guidance, from Defra and the Environment Agency, applies to England. Guidance for Northern Ireland, Scotland and Wales is separate. Its opening warning is that pollution can bring an unlimited fine, prison for up to five years, or both, and the polluter may owe the whole clean-up cost.
It lists oil above ground as petrol, diesel, mineral oil, heating oil, vegetable oil or hydrotreated vegetable oil, each with its own guidance. The Environment Agency pollution incident hotline is the immediate call when polluting materials have entered or could enter a watercourse or soak into the ground. Examples given are a ruptured tank, a leaking pipe and an uncontained spill.
- Secondary containment: the Environment Agency recommends at least 25% of container capacity for containers up to 205 litres, and at least 110% for containers over 205 litres.
- Storage distance: the Environment Agency advises at least 10 m from watercourses, open drains, gullies, unsurfaced areas or porous surfaces, and 50 m from wells, springs or boreholes.
- Spill kits: the guidance says a spill kit suited to the products on site should be available near storage, loading areas and transfer routes. The people involved should know how to use it.
- Response plan: a pollution incident response plan is advised for any type of storage, to limit pollution from a leak, spill or fire.
Canada: section 201 of CEPA 1999
Section 201 of the Canadian Environmental Protection Act, 1999 applies to the substances on Schedule 1 of the Environmental Emergency Regulations (E2 Regulations), except those excluded under subsection 2(2). The duty falls on a person who owned or had charge, management or control of the substance just before the emergency, and on a person who caused or contributed to it. No volume threshold appears on the page. Paragraph 201(1)(a) turns on harm. It applies to an emergency with an immediate or long-term harmful effect on the environment, or one that is or may be a danger to life or health in Canada.
- A verbal notification is due as soon as possible under the circumstances, to the 24-hour authority for the province or territory.
- A written report is also due as soon as possible. Under subsection 18(2), as amended in 2019, it goes to the Regional Director, Environmental Enforcement Directorate, Enforcement Branch, in the region where the emergency occurs.
- A registered facility reports through the Environmental emergencies reporting system with a GCKey and a Schedule 8. An unregistered facility submits a written report.
The person must also take all reasonable measures consistent with protection of the environment and public safety. A reasonable effort to notify members of the public who may be adversely affected is part of the duty.
Sources
- US Electronic Code of Federal Regulations, 40 CFR 112.1 General applicability (SPCC), version of January 1, 2025, read October 16, 2026
- GOV.UK (Defra and Environment Agency), Pollution prevention for businesses, last updated February 12, 2026, read October 16, 2026
- Environment and Climate Change Canada, Environmental emergency regulations: reporting a spill or release, page details February 22, 2022, read October 16, 2026