Utility pruning clearances: the trim-to distances PG&E prints, beside the California and Oregon minimums
In high fire-threat districts, PG&E's standards cite time-of-trim recommendations of 12 feet on distribution lines and 12 to 30 feet on transmission lines. Its transmission minimums run 4 to 15 feet. California and Oregon print regulator minimums.
Checked against the sources at the bottom of this page on October 15, 2026. Rules, fees and pay change: the source has the last word.
This page reports what the official source says. It is not legal advice: ask the office named here. The distances below are utility trim-to figures and regulator minimums for vegetation. They are not the approach limits that apply to workers.
Minimum versus trim-to
A regulator's minimum is the closest vegetation may come to a conductor. A trim-to distance is the clearance a utility aims for on the day of pruning, so that growth stays outside the minimum until the next cycle. California's General Order 95 draws the same line: Rule 35 requires the Table 1 clearances, and its Appendix E recommends larger clearances at the time of trim.
PG&E's distribution standard TD-7102S (revision 2, effective June 20, 2023) lists Rule 35 and Public Resources Code sections 4293 and 4295.5 as the basis of its programme. It notes that sag and sway can range from 1 foot at quarter-span to 4 feet at mid-span, depending on span length, construction and conductor material.
PG&E distribution lines
TD-7102S covers primary conductors from 4 kilovolts up to less than 60 kilovolts, mostly between 4 and 21 kilovolts. Its appendix lists the minimum distance for primary conductors above 750 volts by jurisdiction.
| Jurisdiction | Rule | Distance |
|---|---|---|
| Local responsibility area outside high fire-threat districts | GO 95, Rule 35, year-round | 18 inches |
| High fire-threat district | GO 95, Rule 35, year-round | 4 feet |
| State responsibility area | Public Resources Code 4293, in fire season | 4 feet |
| Federal responsibility area on US Forest Service land | Public Resources Code 4293, in fire season | 4 feet |
The standard adds that vegetation must not come inside the minimum at any time between inspection and one year or the next scheduled work cycle. For circuits under 750 volts, the standard calls for pruning if strain or abrasion of the conductor is observed.
TD-7102S cites Appendix E of General Order 95 as recommending a minimum of 12 feet of clearance at the time of trim in a high fire-threat district. PG&E extends that recommendation to tree work in the High Fire Risk Area map. The standard adds that greater clearances may be advantageous for public safety or service reliability.
PG&E transmission lines
TD-7103S (revision 4, effective January 27, 2025) covers conductors from 60 to 500 kilovolts. It prints three sets of figures for 60 or 70 kV, 115 kV, 230 kV and 500 kV lines.
| Line voltage | Figures as printed |
|---|---|
| 60 or 70 kV | PG&E minimum 4; CPUC Case 13 1.5; Case 14 4; trim recommendation in a high fire-threat district 12 |
| 115 kV | PG&E minimum 10; CPUC Case 13 1.6; Case 14 10; trim recommendation in a high fire-threat district 30 |
| 230 kV | PG&E minimum 10; CPUC Case 13 2.6; Case 14 10; trim recommendation in a high fire-threat district 30 |
| 500 kV | PG&E minimum 15; CPUC Case 13 9.6; Case 14 10; trim recommendation in a high fire-threat district 30 |
Outside a high fire-threat district, the CPUC recommendation at time of trim is 4, 10, 10 and 15 feet for the four voltages, the same as PG&E's own minimums. The procedure says its minimums are meant to meet or exceed every applicable rule, including NERC reliability standard FAC-003-5 and Rule 35.
The NERC minimum vegetation clearance distance rises with elevation. At 0 to 500 feet it is 1.1 feet at 60 or 70 kV, 1.9 feet at 115 kV, 4.0 feet at 230 kV and 7.0 feet at 500 kV. At 14,001 to 15,000 feet it is 1.6, 2.7, 5.4 and 9.1 feet. The procedure calls these the distances needed to prevent flashover and says prudent practice achieves much greater distances at the time of maintenance.
When pruning, TD-7103S says multiple years of vegetation clearance is desired and one year is the minimum.
California Rule 35 text
General Order 95, Rule 35, requires that the Table 1, Cases 13 and 14, clearances between line conductors and vegetation be maintained under normal conditions. It refers readers to Appendix E for tree trimming guidelines. Appendix E, as the PG&E standards cite it, recommends 12 feet at time of trim in high fire-threat districts and 4 feet in other areas for lines between 2,400 and 71,999 volts.
Rule 35 does not apply where a company has made a good-faith effort to get permission and permission was refused or unobtainable. The rule describes that effort as an attempted personal contact and a written communication, both documented.
Oregon minimums
Oregon Administrative Rule 860-024-0016 sets minimum clearances under reasonably anticipated operating conditions. The figures are 10 feet above 200,000 volts, 7.5 feet at 50,001 through 200,000 volts and 5 feet at 600 through 50,000 volts. The 5-foot clearance may be reduced to 3 feet if the vegetation is not readily climbable. Small branches and new growth may intrude if they stay at least six inches from the conductor.
Sources
- Pacific Gas and Electric Company, Utility Standard TD-7102S, Distribution Vegetation Management Program, revision 2, effective June 20, 2023, read October 15, 2026
- Pacific Gas and Electric Company, Utility Procedure TD-7103S, Vegetation Management Transmission Program, revision 4, effective January 27, 2025, read October 15, 2026
- California Public Utilities Commission, General Order 95, Rule 35, Vegetation Management, read October 15, 2026
- Oregon Public Utility Commission, Oregon Administrative Rules 860-024-0016, Minimum Vegetation Clearance Requirements, Cornell Legal Information Institute copy, read October 15, 2026