Corded tools, extension leads and GFCI in trees: what OSHA 3940 and 29 CFR 1926.404 say

OSHA's tree care fact sheet 3940 lists corded electric power tools as something not to use in trees near energized power lines. The ground-fault circuit interrupter duty sits in the construction standard, 29 CFR 1926.404.

Checked against the sources at the bottom of this page on October 21, 2026. Rules, fees and pay change: the source has the last word.

This page reports what the official source says. It is not legal advice: ask the office named here. Two OSHA documents bear on corded tools in trees: the fact sheet Solutions for Tree Care Hazards (OSHA 3940) and the construction wiring standard, 29 CFR 1926.404. A 2021 OSHA inspection memo adds which electrical standards apply to tree work.

The OSHA 3940 line on corded tools

OSHA 3940 is a two-page fact sheet with five columns: traffic control, drop zones, chippers, aerial lifts and power lines. The power lines column opens with the hazard: workers can be electrocuted when a tree limb, a branch or an uninsulated aerial lift touches a live power line. Its prevention list includes the line "Do not use corded electric power tools in trees near energized power lines."

The same list tells workers to treat all overhead power lines and communication cables as energized and to stay at least 10 feet (3 metres) away unless specifically qualified. It also says to use wooden or synthetic ladders near overhead lines, never metal or other conductive ones. The sheet gives no cord length, no extension lead rule and no GFCI wording.

The GFCI duty in 29 CFR 1926.404

Paragraph (b)(1) of 29 CFR 1926.404 covers ground-fault protection on construction sites. The employer uses either ground fault circuit interrupters or an assured equipment grounding conductor program. Both routes are in addition to any other equipment grounding conductor requirements.

For the GFCI route, all 120-volt, single-phase, 15- and 20-ampere receptacle outlets on construction sites need approved ground-fault circuit interrupters for personnel protection. The outlets covered are those not part of the permanent wiring of the building or structure and in use by employees. A two-wire, single-phase portable or vehicle-mounted generator rated not more than 5 kW is excepted when its circuit conductors are insulated from the generator frame and all other grounded surfaces.

The assured grounding program as the alternative

The standard describes the other route in detail. It covers all cord sets, receptacles that are not part of the building, and equipment connected by cord and plug. The program has to be written and available at the jobsite, with one or more designated competent persons.

  • Cord sets, plugs, receptacles and plug-connected equipment are visually inspected before each day's use.
  • Equipment grounding conductors are tested for continuity, and receptacles and plugs are tested for correct attachment of the grounding conductor.
  • Tests happen before first use, after repairs, after any incident that could have damaged the equipment (the standard's example is a cord set that is run over), and at intervals not above 3 months.
  • Cord sets and receptacles that are fixed and not exposed to damage are tested at intervals not above 6 months.

Which electrical standard reaches tree work

The 2021 OSHA memo on inspecting tree care and tree removal operations says many tree hazards fall under the general industry standards in 29 CFR 1910. It says line-clearance tree trimming is covered in part by 29 CFR 1910.269, in part by 1910 Subpart S, and for some tree trimming by the telecommunications standard, 29 CFR 1910.268. The memo points to 1910.269(a)(1)(i)(E) and 1910.331(b) and (c) for the dividing lines.

That memo asks OSHA inspectors to check safe distances from overhead lines for personnel and equipment, booms and aerial lifts included, and the safe handling of tools such as ladders, in line-clearance tree trimming work. It does not mention GFCIs. The GFCI text quoted above is a construction standard, Part 1926, and neither OSHA document says whether it reaches a given tree job.

Where the wording stops

OSHA 3940 words the corded-tool line as a prevention tip, not as a regulation number. The two documents leave several questions open: extension lead length and rating, and cordless tools, which the fact sheet does not mention. For a decision on a particular job, the office to ask is the OSHA area office or the state plan office for the state.