ArbNation Join free

Hazard and danger trees beside power lines: California, Oregon, BPA and Victoria

California's Rule 35 reaches dead, rotten or diseased trees leaning toward lines. Victoria's draft covers a tree an arborist advises is likely to fall onto a line. BPA's hazard is a branch, top or tree that could fall or grow into its safety zone.

Checked against the sources at the bottom of this page on October 15, 2026. Rules, fees and pay change: the source has the last word.

This page reports what the official source says. It is not legal advice: ask the office named here. The material comes from California Public Utilities Commission General Order 95, Rule 35, Oregon Administrative Rule 860-024-0016, a Bonneville Power Administration supplement analysis dated March 13, 2025, and Victoria's draft Electricity Safety (Electric Line Clearance) Regulations 2026. None of the first two uses the words "danger tree". The Victorian text is a draft, not the made regulations. Clearance tables are in utility pruning clearances.

Terms each source uses

How each source describes a tree that threatens a line from outside the clearance zone
SourceTermWhat it covers
California, GO 95 Rule 35Dead, rotten or diseased treesTrees or parts that overhang or lean toward and may fall into a span
Oregon, OAR 860-024-0016Readily climbable vegetation; cycle busterVegetation a child could climb near a line, and growth that will not last the trim cycle
BPAHazard; danger treesBranches, tops or whole trees that could fall or grow into the minimum safety zone
Victoria, draft codeHazard treeA tree an arborist advises is likely to fall onto or touch a line

California, Rule 35

General Order 95 applies to overhead supply and communication lines, including those on land owned by California state and local agencies. Rule 35 covers a company that has actual knowledge, through normal operating practices or notification, of a problem tree. The tree is dead, rotten or diseased, or has such a portion, and overhangs or leans toward a span it may fall into. Those trees or portions should be removed.

Exception 2 releases the company from Rule 35 where it made a good faith effort to get permission and permission was refused or unobtainable. A good faith effort is documentation of at least one attempted personal contact and one written communication, with proof of mailing or delivery. Exception 4 exempts mature trees whose trunks and limbs sit more than six inches from the conductor, but less than the Table 1 clearance, if strong enough to stay off the conductor. The utility bears the risk of that call, and the Commission has final authority.

Oregon, OAR 860-024-0016

The rule sets minimum clearances: 10 feet above 200,000 volts, 7.5 feet from 50,001 through 200,000 volts, and 5 feet from 600 through 50,000 volts, reduced to 3 feet where the vegetation is not readily climbable. Readily climbable vegetation has low limbs reachable from the ground and close enough together for a child or average person to climb without a ladder. It also has a main stem or branch that would support the climber within arm's reach of an uninsulated energized line, or near enough to cause injury.

Operators trim or remove readily climbable vegetation to limit access to a high voltage conductor. A cycle buster is vegetation that will not make it through the routine trim cycle without encroaching on the clearance. In deciding the extent of work, the operator considers voltage, location, configuration, conductor sag, and the growth habit, strength and health of adjacent vegetation, including rates of tree mortality. The rule does not define a danger tree.

Bonneville Power Administration

The supplement analysis, number DOE/EA/EIS-0285/SA-912, covers about 130 miles of transmission corridor in Crook, Deschutes, Lake and Klamath counties, Oregon. BPA states that, to comply with Western Electricity Coordinating Council standards, it proposes to manage vegetation with the goal of removing tall-growing vegetation that is or will soon become a hazard. It defines a hazard as one or more branches, tops or whole trees that could fall or grow into the minimum safety zone and cause an electrical arc, relay or outage.

Under that analysis BPA proposes to remove about 10 danger trees in or beside two transmission rights-of-way, and landowners are notified about three weeks before work. The document does not define danger trees.

Victoria, draft regulations

Clause 9 of Schedule 1, the draft Code of Practice, applies to a responsible person under section 84, 84C or 84D of the Electricity Safety Act 1998. That person may prune or remove a tree if a suitably qualified arborist has assessed it for foreseeable local conditions. The arborist must have advised that the tree, or part of it, is likely to fall onto or otherwise contact an electric line. The clause adds that it does not matter that the tree is outside, and unlikely to grow into, the minimum clearance space.

Clause 8 requires an owner or operator of a transmission line to manage adjacent trees to avoid, as far as practicable, a tree entering the minimum clearance space if it falls. Pruning follows AS 4373, and the draft limits the pruning and removal of significant trees.

Sources