Step and touch potential and ground gradient: how OSHA and Cal/OSHA define them
OSHA's appendix on hazardous differences in electric potential defines ground potential gradient, step potential and touch potential. Cal/OSHA prints the same appendix text in its High-Voltage Electrical Safety Orders.
Checked against the sources at the bottom of this page on October 21, 2026. Rules, fees and pay change: the source has the last word.
OSHA's Appendix C to 29 CFR 1910.269 is titled "Protection From Hazardous Differences in Electric Potential". It explains why a grounded object that touches an energised line puts voltage on the object and on the ground around it. The examples are a crane and a de-energised power line that has been grounded.
The terms
| Term | Meaning in the appendix |
|---|---|
| Absolute (true) ground | The reference point. It always sits at 0 volts above ground potential. |
| Ground potential gradient | The spread of voltage outward from a grounding electrode or grounding point during a ground fault. The voltage falls quickly as distance from the electrode grows. |
| Ground potential | The voltage drop that goes with that spreading. |
| Step potential | The voltage between the feet of a person standing near an energised grounded object, the electrode. It equals the difference in voltage between the two points where the feet rest, at different distances from the electrode. |
| Touch potential | The voltage between the energised grounded object and the feet of a person in contact with it. It can come close to the full voltage across the object if the object is grounded at a point remote from where the person touches it. |
| Equipotential zone | An area where voltage is equalised, for example with a metal mat or a grounding grid connected to the grounded object, or by bonding conductive objects in the work area. It protects workers inside it from hazardous step and touch potentials. |
| Ground | A conducting connection between a circuit or equipment and the earth, or to a conducting body that stands in for the earth. |
| Bond | The electrical interconnection of conductive parts designed to maintain a common electric potential. |
| Ground mat (grounding grid) | A temporary or permanent metallic mat or grating that makes an equipotential surface and gives connection points for grounds. |
Why a person can be at risk without touching the line
The appendix explains that a person could be at risk of injury during a fault simply by standing near the grounded object. Its worked example is a crane grounded to the system neutral that contacts an energised line. Anyone in contact with the crane or its uninsulated load line is exposed to a touch potential nearly equal to the full fault voltage. The degree of hazard depends on the size of the current through the person and the time of exposure.
Ways the appendix describes protecting people on the ground
For workers on the ground, the appendix lists three methods an employer may use: equipotential zones, insulating equipment and restricted work areas. An equipotential zone does not protect anyone standing wholly or partly outside it. Insulating equipment such as rubber gloves must be rated for the highest voltage that can be impressed on the grounded objects under fault conditions, rather than for the full system voltage. Under the third method, workers near transmission structures stay at a distance where step voltages would be too low to cause injury. The appendix also says an engineering analysis of the power system under fault conditions can show whether hazardous step and touch voltages will develop.
The same text in the construction and California rules
Appendix C to Subpart V of 29 CFR Part 1926 carries the same introduction, definitions and sections as the general industry appendix. California prints it as Appendix E to Article 36, Work Procedures and Operating Procedures, in the High-Voltage Electrical Safety Orders of Title 8. The wording of the terms matches across all three.
The guide to electrical contact in tree work covers the contact hazard itself, and the guide on a tree or truck that touches a power line covers the event.