Wood chip fuel grades: EN ISO 17225-4 classes

EN ISO 17225-4:2021 sets fuel classes for graded wood chips made with sharp tools. Natural Resources Canada prints the limits as four grades, A1, A2, B1 and B2, with ash from 1.0 to 3.0 percent of dry weight.

Checked against the sources at the bottom of this page on October 21, 2026. Rules, fees and pay change: the source has the last word.

This page reports what the official source says. It is not legal advice: ask the office named here. The standard itself is sold, not published free. Its scope comes from the catalogue pages of the Estonian and Norwegian standards bodies, and the class limits come from a 2016 Natural Resources Canada bulletin that restates the Canadian adoption, CAN/CSA-ISO 17225 Part 4.

The standard and its editions

EN ISO 17225-4 as listed by two national standards bodies
ItemEntry
TitleSolid biofuels: Fuel specifications and classes, Part 4: Graded wood chips
Current editionEN ISO 17225-4:2021, listed as valid from March 15, 2021 by EVS; published March 25, 2021 by Standards Norway
Earlier editionEN ISO 17225-4:2014 (EVS lists it from June 5, 2014; Standards Norway shows it as withdrawn and replaced by the 2021 edition)
ClassificationICS 27.190 and 75.160.40

EVS and Standards Norway print the same scope. The standard determines the fuel quality classes and specifications of graded wood chips. It covers only chips from forest, plantation and other virgin wood (ISO 17225-1 class 1.1), by-products and residues from the wood processing industry (1.2) and chemically untreated used wood (1.3.1). It covers only chips produced with sharp tools and does not cover hog fuel, which is produced with blunt tools.

Grades and limits as Natural Resources Canada prints them

Solid Biofuels Bulletin No. 6, Graded Wood Chips (Natural Resources Canada, 2016, 5 pages), says the CAN/CSA-ISO 17225 Part 4 classification is based on origins and sources and provides for four grades. The bulletin names moisture, particle size and ash as the most critical properties.

Table 1 of the NRCan bulletin: moisture and ash by grade
GradeMoisture, weight %Ash, weight % dry
A1M10 up to 10; M25 up to 25A1.0 up to 1.0
A2M35 up to 35A1.5 up to 1.5
B1Maximum value to be statedA3.0 up to 3.0
B2Maximum value to be statedA3.0 up to 3.0

The bulletin describes the grades by source. Grade A (A1 and A2) comes mainly from stem wood (classification 1.1.3) and from milling (1.2.1) and logging (1.1.4) by-products and residues. A1 chips are dried and have lower ash and no or little bark, while A2 has slightly higher ash or moisture. Grade B1 draws on tree trimmings, prunings and arboriculture work in city parks (1.1.7). Grade B2 adds chemically treated by-products and residues from wood processing (1.2.2) and chemically untreated used wood (1.3.1), and contains no heavy metals or halogenated organic compounds from preservatives or coatings.

Particle size classes

Table 2 of the NRCan bulletin: particle size classes
ClassMain fraction and finesCoarse fraction and longest particle
P16SAt least 60% by weight from 3.15 to 16 mm; fines of 3.15 mm or less at 15% or less6% or less over 31.5 mm; longest particle 45 mm
P31SAt least 60% from 3.15 to 31.5 mm; fines 10% or less6% or less over 45 mm; longest particle 150 mm
P45SAt least 60% from 3.15 to 45 mm; fines 10% or less10% or less over 63 mm; longest particle 200 mm

Particle size is tested by ISO 17827-1 or -2, and moisture by CAN/CSA-ISO 18134-1 or -2. The bulletin calls an oven-dry analysis more accurate than a hand-held meter and says the common names hog fuel and shavings are not quantitative enough for fuel supply agreements. The minimum label gives the source class, particle size, moisture and ash. Its example reads origin logging residues (1.1.4), P45S, moisture M40, ash A1.5. That label means at least 60% of the chips lie between 3.15 and 45 mm, with moisture under 40% and ash under 1.5%.

What the sources leave open

The bulletin and the 2021 standard may differ. The bulletin does not name the edition of the Canadian adoption it summarises, and its Table 1 gives no moisture class for B1 and B2. The two catalogue pages print the title, edition and scope only.