California PRC 4293 clearances: how 14 CCR 1250 to 1258 and GO 95 Rule 35 apply them

California's 14 CCR 1256 measures PRC 4293 clearance in a 360-degree arc around the conductor. 14 CCR 1257 exempts insulated wire and some mature trees, and GO 95 Rule 35 sets its own clearances.

Checked against the sources at the bottom of this page on October 15, 2026. Rules, fees and pay change: the source has the last word.

This page reports what the official source says. It is not legal advice: ask the office named here. It draws on Title 14 of the California Code of Regulations, Article 4 (sections 1250 to 1257), the California Public Utilities Commission's General Order 95, Rule 35, and one utility standard that tabulates both.

Purpose and reach of Article 4

Section 1250 gives the purpose of Article 4. It provides specific exemptions from electric pole and tower firebreak clearance standards and from electric conductor clearance standards, and it specifies when and where the standards apply. Its authority citation is Public Resources Code (PRC) sections 4292 and 4293.

Section 1252 sets where the rules apply. The Director applies PRC 4292 to 4296 in any mountainous, forest covered, brush covered or grass covered land within State Responsibility Areas, unless 14 CCR 1255 or 1257 exempts it. Section 1253 sets when they apply: during the declared CAL FIRE fire season for the county, which the Director posts on the department web site.

The 360-degree rule in section 1256

Section 1256 says the minimum clearance PRC 4293 requires must be kept at the specified distances. They are measured at a right angle to the conductor axis, at any location, outward through an arc of 360 degrees.

The minimum clearance includes two positions. One is any position through which the conductor may move, considering the size and material of the conductor and its span length. The other is any position through which the vegetation may sway, considering climate, foreseeable wind velocities and temperature, and the location, height and species of the vegetation.

Exemptions in section 1257

Section 1257 exempts the PRC 4293 minimum clearance in State Responsibility Areas in three cases. The first covers conductors of three kinds.

  • Conductors that are insulated tree wire with its high density, abrasion resistant outer covering intact.
  • Conductors that are insulated self-supporting aerial cable with the insulation intact.
  • Conductors supported by sound and living tree trunks from which all dead or decadent branches have been removed.

The second case is the areas described in 14 CCR 1255(c). The third covers mature trees, called Exempt Trees. Their trunks and major limbs sit more than six inches from primary distribution equipment, but closer than the PRC 4293 distance. The regulation describes the equipment as conductor and energy carrying hardware, "generally less than 35 kilovolts".

An Exempt Tree must meet three criteria, confirmed by a Certified Arborist or a Registered Professional Forester. The tree or limb is six inches or more from the line at all times. The tree or limb is at least six inches in diameter at the conductor level. The tree has no scaffold branches below eight and one-half feet from the ground, so it cannot be easily climbed.

Utilities with primary distribution conductors in State Responsibility Areas must inspect Exempt Trees annually. They must keep a database with latitude and longitude, species and last inspection date, and report it to CAL FIRE by July 1 each year. When building or maintaining primary equipment, they must prevent new Exempt Trees to the extent feasible. If a conductor has or will touch an Exempt Tree, the tree is altered or an engineering solution is applied, and the action goes in the database. The exemptions do not apply to Hazard Trees.

GO 95 Rule 35

CPUC General Order 95, Rule 35 covers vegetation where overhead conductors cross trees. The minimum clearances in Table 1, Cases 13 and 14, measured between line conductors and vegetation under normal conditions, shall be maintained. Appendix E carries tree trimming guidelines. The rule applies to all overhead electrical supply and communication facilities the order covers, including those on lands of California state and local agencies.

The rule treats dead, rotten or diseased trees that overhang or lean toward a span differently. When a company has actual knowledge of them, they should be removed. Circuits at 750 volts or less should be kept clear of vegetation in new construction and rebuilds, whenever practicable. Where such a circuit shows strain or abrasion from vegetation, the condition shall be corrected by reducing tension, rearranging or replacing the conductor, pruning, or adding mechanical protection. Contact between vegetation and conductors does not by itself make a nonconformance.

The rule lists four exceptions.

  1. Conductors under 60,000 volts where trimming is not practicable and the conductor is separated from the tree by suitable materials.
  2. Cases where the company made a good faith effort to get permission and was refused or could not obtain it. Rule 35 defines that effort as a documented personal contact attempt and a written communication.
  3. Unusual circumstances beyond the utility's control, where the Commission may still direct prompt remedial action.
  4. Mature trees more than six inches, but less than the Table 1 Case 13E and 14E clearance, from primary distribution conductors. The trunk or limb must be strong enough to keep out of the six inches under foreseeable wind and weather. The utility bears the risk of deciding whether this applies, and the Commission has final authority.

One utility's reading of both rules

Pacific Gas and Electric's standard TD-7102S, Revision 2, effective June 20, 2023, lists the rules it follows. They are GO 95 Rule 35, Rule 35 in Appendix E, Rule 18, PRC 4293 and 4295.5, and 14 CCR sections 1250 to 1253, 1256, 1257 and 1258. Its Appendix A gives the minimum distance for primary conductors above 750 volts by jurisdiction.

JurisdictionRule PG&E appliesDistance
Local Responsibility Area, outside High Fire-Threat DistrictGO 95 Rule 35, year-round18 inches
High Fire-Threat DistrictGO 95 Rule 35, year-round4 feet
State Responsibility AreaPRC 4293, during fire season4 feet
Federal Responsibility Area on USFS propertyPRC 4293, during fire season4 feet

For conductors under 750 volts the standard says to prune if strain or abrasion is observed. It notes that sag and sway can range from 1 foot at quarter-span to 4 feet at mid-span. Appendix E of Rule 35 recommends a minimum 12 feet of clearance at time of trim in the High Fire-Threat District, and the standard extends that to tree work in High Fire Risk Areas.

Sources