Insulated tools and aerial devices near energised conductors: the standards and tests regulators name
OSHA prints test voltages and a two-year examination cycle for live-line tools, and cites ANSI A92.2 for aerial lift electrical tests. WorkSafeBC sets a 12-month dielectric test for insulated platforms.
Checked against the sources at the bottom of this page on October 19, 2026. Rules, fees and pay change: the source has the last word.
The named regulations are described here as published. It is not training and does not teach the work. The facts come from OSHA's rules for electric power work and aerial lifts and from the WorkSafeBC Occupational Health and Safety Regulation.
OSHA 1910.269: live-line tools
Section 1910.269(j)(1) sets minimum tests for the rods, tubes and poles of live-line tools. A fibreglass-reinforced plastic tool is to withstand 328,100 volts per metre (100,000 volts per foot) of length for 5 minutes. A wood tool is to withstand 246,100 volts per metre (75,000 volts per foot) for 3 minutes. Other tests the employer can show to be equivalent also count.
A note to the paragraph deems tools made of rod and tube that meet ASTM F711-02 (2007), the standard specification for fibreglass-reinforced plastic rod and tube used in live-line tools, to comply.
Under paragraph (j)(2), each live-line tool is wiped clean and visually inspected for defects before use each day. A tool with a defect or contamination that could affect its insulating qualities or mechanical integrity is removed from service. It is examined and tested before it returns to service.
Tools used for primary employee protection are removed from service every 2 years for examination, cleaning, repair and testing. The test method must verify integrity along the entire working length and, for fibreglass, under wet conditions. The test voltage is 246,100 volts per metre (75,000 volts per foot) for 1 minute on fibreglass, and 164,000 volts per metre (50,000 volts per foot) for 1 minute on wood.
OSHA 1910.269: line-clearance tree trimming and mechanical equipment
Paragraph (r)(1)(iv) allows branches that contact exposed energised conductors, or lie within the distances in Tables R-5 to R-8, to be removed only with insulating equipment. A note treats a tool made of material that meets the (j)(1) insulating tests as insulated when it is clean and dry. Paragraph (r)(1)(v) bars ladders, platforms and aerial devices from coming closer to an energised part than those table distances.
Paragraph (p)(4) covers mechanical equipment near energised lines. The insulated portion of an aerial lift operated by a qualified employee in the lift is exempt from the minimum approach distance. The exemption holds if the approach distance is kept between the uninsulated portions of the lift and objects at a different potential. Where equipment could become energised, one option is equipment insulated for the voltage involved.
OSHA 1910.67: aerial lifts
Section 1910.67 defines an insulated aerial device as an aerial device "designed for work on energized lines and apparatus". The insulated portion of an aerial lift may not be altered in any manner that might reduce its insulating value. Lift controls are tested each day before use.
Paragraph (c)(3) requires electrical tests in conformance with Section 5 of ANSI A92.2-1969. An equivalent DC voltage test may replace the AC test where the equipment manufacturer or an equivalent entity approves it.
WorkSafeBC Part 19
Section 19.9 of the British Columbia regulation requires an insulated elevating work platform to be dielectrically tested at least every 12 months under section 5.3.4 of CSA CAN/CSA-C225-10, Vehicle-mounted aerial devices. The testing agency certifies the platform's insulating capability. A platform that fails is treated as non-insulated. Its insulated markings come off, its records and manuals say non-insulated, and workers are told before use.
Section 19.34 requires vegetation closer to an energised high voltage conductor than the column B limit in Table 19-3 to be cut with approved insulated tools. A certified utility arborist may use an insulated tool acceptable to the Board up to the column A limit. From an insulated aerial device, the arborist may work closer than the column A limit, up to but not touching a conductor of 75 kV or less.
| Phase-to-phase voltage | A: insulated tool limit | B: work limit, certified | C: work limit, apprentice |
|---|---|---|---|
| Over 750 V to 20 kV | 0.3 m (1 ft) | 0.9 m (3 ft) | 3 m (10 ft) |
| Over 20 kV to 30 kV | 0.5 m (1.5 ft) | 1.2 m (4 ft) | 3 m (10 ft) |
| Over 30 kV to 75 kV | 0.9 m (3 ft) | 1.5 m (5 ft) | 3 m (10 ft) |
| Over 75 kV to 250 kV | 2.1 m (7 ft) | 3 m (10 ft) | 4.5 m (15 ft) |
| Over 250 kV to 325 kV | 2.6 m (8.5 ft) | 4.5 m (15 ft) | 6 m (20 ft) |
| Over 325 kV to 550 kV | 3.7 m (12 ft) | 6 m (20 ft) | 6 m (20 ft) |
Section 19.35 requires insulated tools to be used, stored, tested and maintained as section 19.16(2)(c) sets out. Insulated hand tools and insulated aerial devices are kept clean and dielectrically tested to a standard acceptable to the Board. A note states that an insulated aerial device is not considered an insulated tool.